570 9424200994 Rev N
Reactive Power
5 Ampere CT Range ................................................. 7,500 var to +7,500 var
1 Ampere CT Range ................................................. 1,500 var to +1,500 var
Accuracy.................................................................... ±3% at zero power factor
Energy Data Reporting
5 Ampere CT Range ................................................. 1,000 GWh or 1,000 Gvarh
1 Ampere CT Range ................................................. 1,000 GWh or 1,000 Gvarh
Units of Measure ....................................................... kilo
Rollover Value of Registers....................................... 1,000,000,000 kWhr or kvarhr
Accuracy.................................................................... ±3% at unity power factor
21 - Distance Protection
Diameter
Setting Range ........................................................ 0 to 500
5 Ampere CT Accuracy .......................................... ±5% or ±0.4 , whichever is greater from 0 to 100
1 Ampere CT Accuracy .......................................... ±5% or ±0.4 , whichever is greater from 0 to 500
Time Delay
Setting Range ........................................................ 0 to 300,000 ms
Accuracy................................................................. ±1.5% or ±4 cycles, whichever is greater
Torque Angle
Setting Range ........................................................ 0 to 90 degrees
Accuracy................................................................. ±1 degree
Offset
Setting Range ........................................................ 500 to 500
5 Ampere CT Accuracy .......................................... ±5% or ±0.4 , whichever is greater from 100 to 100
1 Ampere CT Accuracy .......................................... ±5% or ±0.4 , whichever is greater from 500 to 500
24 - Overexcitation Protection
Inverse Time
Curve Exponent ........................................................ 0.5, 1, or 2
Pickup
Setting Range ........................................................... 0.5 to 6 V/Hz
Accuracy.................................................................... ±2% or ±0.05 V/Hz, whichever is greater
Dropout/Pickup Ratio ................................................ 98% ±1%
Time Dial
Setting Range ........................................................... 0.0 to 9.9
Accuracy.................................................................... ±5% or ±3 cycles, whichever is greater
Reset Dial
Setting Range ........................................................... 0.0 to 9.9
Accuracy.................................................................... ±5% or ±3 cycles, whichever is greater
Definite Time 1 and 2
Pickup
Setting Range ........................................................... 0.5 to 6 V/Hz
Accuracy.................................................................... ±2% or ±0.05 V/Hz, whichever is greater
Time Delay
Setting Range ........................................................... 50 to 600,000 ms
Accuracy.................................................................... ±1.5% or ±4 cycles, whichever is greater
Specifications - 25 Hz Operation BE1-11g