9424200994 Rev N 309
Table 101. Default Function Block Logic
Function Purpose
BESTlogicPlus
Inputs
50-1
Used for instantaneous phase overcurrent protection.
0
50-2
Used for instantaneous neutral overcurrent protection.
0
50-3
Used for instantaneous negative-sequence overcurrent protection.
0
51-1
Used for timed phase overcurrent protection.
0
51-2
Used for timed neutral overcurrent protection.
0
51-3
Used for timed negative-sequence overcurrent protection.
0
FAULT TRIGGER
Trip
Trip Bus
Picked Up
Pickup Bus
Logic
0
Table 102. Default Output Logic
Output Purpose Description Label
State Labels
Energized
De-
Energized
OUTA Alarm Output Contact.
Alarm contact closes/opens (refer
to style number) automatically
when relay trouble alarm occurs.
Output
Alarm
On Off
OUT1 Breaker Trip Output.
Contact closes when protective
trip expression is TRUE.
Output
1
On Off
OUT2
Instantaneous Phase
OC Auxiliary Contact.
Contact closes when
instantaneous overcurrent (50-1)
trip occurs.
Output
2
On Off
OUT3
Timed Phase OC
Auxiliary Contact.
Contact closes when inverse
overcurrent (51-1) trip occurs.
Output
3
On Off
OUT4
Instantaneous Neutral
and Negative-
Sequence OC.
Contact closes when
instantaneous overcurrent (50-2
or 50-3) trip occurs.
Output
4
On Off
OUT5
Timed Neutral and
Negative-Sequence
OC.
Contact closes when inverse
overcurrent (51-2 or 51-3) trip
occurs.
Output
5
On Off
BE1-11g BESTlogicPlus