498 9424200994 Rev N
Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus Programmable Logic shown in Figure
311.
Blocking is disabled.
OUT1 closes for 40Q Trip.
OUT2 closes for 40Q Pickup.
Fault recording is enabled.
Figure 311. BESTlogicPlus Settings
Step 3: Use BESTCOMSPlus to open the Protection, Power, Loss of Excitation - Reverse Var Based
(40Q) screen and send the first row of test settings in Table 228 to the BE1-11g.
Table 228. Pickup Test Settings
Pickup Setting
Time Delay
500 var
50 ms
1,000 var
50 ms
2,000 var
50 ms
Step 4: Connect and apply a 100 Vac, three-phase voltage source at nominal frequency to terminals
C13 (A-phase), C14 (B-phase), C15 (C-phase), and C16 (Neutral). Connect a variable ac
current source to terminals D1 (A-phase polarity) and D2 (A-phase non-polarity).
Step 5: Set A-phase current to lag the voltage by 90 degrees and slowly increase the current from
0 amps until OUT2 closes and record the pickup. Verify the 40Q target on the front-panel
display. Decrease the A-phase current until OUT2 opens and record the dropout.
Step 6: With the BE1-11g picked up (OUT2 closed), change the angle of the applied current to
90 degrees I lag E and verify that OUT2 opens. This verifies that the 40Q function is operating
on leading var.
Step 7: Repeat steps 5 and 6 for the 1,000 var and 2,000 var pickup settings in Table 228. Record the
results.
Step 8: (Optional.) Repeat steps 1 through 7 for settings group 1, 2, and 3.
Timing Verification
Step 1: Use BESTCOMSPlus to open the Protection, Power, Loss of Excitation - Reverse Var Based
(40Q) screen and send the first row of test settings in Table 229 to the BE1-11g for settings
group 0.
Table 229. Timing Test Settings
Pickup Setting
Time Delay
500 var
2,000 ms
500 var
5,000 ms
500 var
10,000 ms
Loss of Excitation - Reverse Var Based (40Q) Test BE1-11g