Basler-electric BE1-11g Instrukcja Użytkownika Strona 480

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 672
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 479
468 9424200994 Rev N
Setting
Value
BESTCOMSPlus Screen
Description
Element Mode
IA
Protection, Current,
Instantaneous Overcurrent (50-1)
Enables 50-1 function for
IA mode
Direction
Forward
Protection, Current,
Instantaneous Overcurrent (50-1)
Selects forward direction
for 50-1
Element Mode
3I0
Protection, Current,
Instantaneous Overcurrent (50-2)
Enables 50-2 function for
3I0 mode
Direction
Forward
Protection, Current,
Instantaneous Overcurrent (50-2)
Selects forward direction
for 50-2
Element Mode
I2
Protection, Current,
Instantaneous Overcurrent (50-3)
Enables 50-3 function for
I2 mode
Direction
Forward
Protection, Current,
Instantaneous Overcurrent (50-3)
Selects forward direction
for 50-3
50-1 67 A
Enabled
Target Configuration, Targets
Enables phase A
directional target for 50-1
50-2 67 Residual
Enabled
Target Configuration, Targets
Enables residual
directional target for 50-2
50-3 67 Neg SEQ
Enabled
Target Configuration, Targets
Enables Neg SEQ
directional target for 50-3
Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus programmable logic shown in Figure 306.
Blocking is disabled.
OUT1 closes for 50-1 Trip.
OUT2 closes for 50-2 Trip
OUT3 closes for 30-3 Trip.
Fault recording is enabled for 50-1, 50-2, and 50-3.
Figure 306. BESTlogicPlus Settings
Step 3: Using Table 213 as a guide, send the settings to the BE1-11g. Prior to each directional test,
reset the BE1-11g targets from the previous test. Max Torque Angle setting, for positive and
Directional Overcurrent (67) Test BE1-11g
Przeglądanie stron 479
1 2 ... 475 476 477 478 479 480 481 482 483 484 485 ... 671 672

Komentarze do niniejszej Instrukcji

Brak uwag