508 9424200994 Rev N
Step
Pickup Setting
Low
Actual Pickup
High
Pass/Fail
5
10.0 V (5
)
9.70 V
10.3 V
P / F
6
8.00 V
7.92 V
8.08 V
P / F
Pickup Verification (mho Characteristic 2)
Step
Pickup Setting
Low
Actual Pickup
High
Pass/Fail
5
10.0 V (5 )
9.70 V
10.3 V
P / F
6
8.00 V
7.92 V
8.08 V
P / F
Timing Verification (mho Characteristic 1)
Time Delay Range = 0 to 300,000 ms
Timing Accuracy = ±0.5% or ±2 cycles, whichever is greater
Step
Time Delay Setting
Low
Actual Timing
High
Pass/Fail
4
2,000 ms
1,967 ms
2,033 ms
P / F
5
1,000 ms
967 ms
1,033 ms
P / F
Timing Verification (mho Characteristic 2)
Step
Time Delay Setting
Low
Actual Timing
High
Pass/Fail
4
2,000 ms
1,967 ms
2,033 ms
P / F
5
1,000 ms
967 ms
1,033 ms
P / F
Loss of Excitation Impedance Based (40Z) Test BE1-11g