9424200994 Rev N 465
4
5.0
I2
0.50 A
1.798 sec
1.988 sec
P / F
4
5.0
I2
2.50 A
0.944 sec
1.044 sec
P / F
4
9.9
I2
0.20 A
8.300 sec
9.173 sec
P / F
4
9.9
I2
0.50 A
3.535 sec
3.907 sec
P / F
4
9.9
I2
2.50 A
1.844 sec
2.038 sec
P / F
Timing Verification (IG Mode, SEF)
Time Dial Range = 0.0 to 9.9
Timing Accuracy = ±5% or ±cycles, whichever is greater
Step
Time Dial
Time Curve
Applied Current
Low
Actual Timing
High
Pass/Fail
4
0.5
I2
0.20 A
0.444 sec
0.491 sec
P / F
4
0.5
I2
0.50 A
0.190 sec
0.240 sec
P / F
4
0.5
I2
0.80 A
0.149 sec
0.197 sec
P / F
4
5.0
I2
0.20 A
4.204 sec
4.647 sec
P / F
4
5.0
I2
0.50 A
1.798 sec
1.988 sec
P / F
4
5.0
I2
0.80 A
1.401 sec
1.548 sec
P / F
4
9.9
I2
0.20 A
8.300 sec
9.173 sec
P / F
4
9.9
I2
0.50 A
3.535 sec
3.907 sec
P / F
4
9.9
I2
0.80 A
2.674 sec
3.111 sec
P / F
BE1-11g Inverse Overcurrent (51) Test