444 9424200994 Rev N
Dropout should occur between 93-99% of the actual pickup value.
Actual
Actual
6
1.5 0.42 1.26 0.57 1.71 0.46 1.38 0.49 1.47 P / F
7
15.0 4.85 14.55 5.15 15.45 4.65 13.95 4.95 14.85 P / F
7
27.0 8.73 26.19 9.27 27.81 8.37 25.11 8.91 26.73 P / F
6
0.3 0.08 0.24 0.11 0.33 0.093 0.279 0.099 0.297 P / F
7
3.0 0.97 2.91 1.03 3.09 0.93 2.79 0.99 2.97 P / F
7
5.4 1.74 5.22 1.85 5.55 1.67 5.01 1.78 5.34 P / F
* Dropout range is calculated from the pickup setting and may need adjusted based on actual pickup.
Timing Verification (I2 Mode)
Time Delay Range = 0 to 60,000 ms
Timing Accuracy = ±0.5% or ±½ cycle, whichever is greater + 3 cycles max for currents 1.5 x pickup
Pickup Verification (IG Mode)
Pickup Setting Range = 0.5 to 150 A for 5A sensing
0.1 to 30 A for 1A sensing
0.01 to 7.5 for SEF
Pickup Accuracy = ±2% or ±50 mA, whichever is greater for 5A sensing
±2% or ±10 mA, whichever is greater for 1A sensing
±2.5% or ±2.5 mA, whichever is greater for SEF
Dropout should occur between 93-99% of the actual pickup value.
* Dropout range is calculated from the pickup setting and may need adjusted based on actual pickup.
Instantaneous Overcurrent (50) Test BE1-11g
Komentarze do niniejszej Instrukcji