Basler-electric BE1-11g Instrukcja Użytkownika Strona 101

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 672
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 100
9424200994 Rev N 89
Table 29. Logic Inputs and Outputs
Name
Logic Function
Purpose
Block
Input
Disables the 50 function when true
Trip
Output
True when the 50 element is in a trip condition
Pickup
Output
True when the 50 element is in a pickup condition
Operational Settings
Instantaneous overcurrent element operational settings are configured on the Instantaneous Overcurrent
(50) settings screen (Figure 59) in BESTCOMSPlus. Setting ranges and defaults are summarized in
Table 30.
Figure 59. Instantaneous Overcurrent Settings Screen
Table 30. Operational Settings
Setting
Range
Increment
Unit of Measure
Default
Mode
Disabled, IA, IB, IC, 3 Phase,
3I0, I1, I2, IG, or Unbalance
n/a n/a Disabled
Source*
CT Circuit 1 or CT Circuit 2
n/a
n/a
CT Circuit 1
Pickup
0 or 0.5 to 150 (5A CTs)
0 or 0.1 to 30 (1A CTs)
0 or 0.01 to 7.5 (SEF)
varies amps
0
2 to 100 (Unbalance mode)
1
percent
Time Delay
0 to 60,000
varies
milliseconds
0
Direction
Forward, Reverse, or Non-Directional
n/a
n/a
Non-Directional
* For protection systems equipped with two sets of CTs.
BE1-11g Instantaneous Overcurrent (50) Protection
Przeglądanie stron 100
1 2 ... 96 97 98 99 100 101 102 103 104 105 106 ... 671 672

Komentarze do niniejszej Instrukcji

Brak uwag