Basler-electric BE1-11g Instrukcja Użytkownika Strona 441

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 672
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 440
9424200994 Rev N 429
Step 2: Use BESTCOMSPlus to configure the BESTlogicPlus programmable logic shown in Figure 293.
Blocking is disabled.
OUT1 closes for 81-1 Trip.
OUT2 closes for 81-1 Pickup.
Fault recording is enabled.
Figure 293. BESTlogicPlus Settings (Underfrequency)
Step 3: Use BESTCOMSPlus to open the Protection, Frequency, Frequency (81-1) screen and send
the first row of test settings in Table 177 to the BE1-11g.
Table 177. Pickup Test Settings (Underfrequency)
Pickup Setting
Time Delay
42 Hz
0 ms
46 Hz
0 ms
48 Hz
0 ms
Step 4: Prepare to monitor the 81-1 function operation. Operation can be verified by monitoring OUT2
(see Figure 293).
Step 5: Connect and apply a 120 Vac, 60-hertz voltage source to terminals C13 (A-phase) and C16
(neutral).
Step 6: Slowly decrease the frequency of the applied voltage until OUT2 closes and record the pickup.
Verify that there is an 81-1-Under target on the front-panel display. Slowly increase the
frequency until OUT2 opens and record the dropout.
Step 7: Repeat Step 6 for the 46 Hz and 48 Hz pickup settings listed in Table 177. Record the results.
Step 8: (Optional.) Repeat steps 1 through 7 for settings groups 1, 2, and 3.
Step 9: (Optional.) Repeat steps 1 through 8 for 81-2, 81-3, 81-4, 81-5, 81-6, 81-7, and 81-8.
Time Delay Verification
Step 1: Use BESTCOMSPlus to open the Protection, Frequency, Frequency (81-1) screen and send
the first row of test settings in Table 178 to the BE1-11g. Commands entered in Table 176
should be retained for this test.
Table 178. Timing Test Settings
Pickup Setting
Time Delay
57.50 Hz
2,000 ms
57.50 Hz
5,000 ms
57.50 Hz
10,000 ms
BE1-11g Frequency (81) Test
Przeglądanie stron 440
1 2 ... 436 437 438 439 440 441 442 443 444 445 446 ... 671 672

Komentarze do niniejszej Instrukcji

Brak uwag