9424200994 Rev N 389
Step
Dropout Delay Setting
Low
Actual Timing
High
Pass/Fail
6
VTP - Dead V Dropout Delay - 5000 ms
4,968 ms
5,032 ms
P / F
6
VTP - Live V Dropout Delay - 5000 ms
4,968 ms
5,032 ms
P / F
7
VTX - Dead V Dropout Delay - 50 ms
18 ms
82 ms
P / F
7
VTX - Live V Dropout Delay - 50 ms
18 ms
82 ms
P / F
7
VTX - Dead V Dropout Delay - 2000 ms
1,968 ms
2,032 ms
P / F
7
VTX - Live V Dropout Delay - 2000 ms
1,968 ms
2,032 ms
P / F
7
VTX - Dead V Dropout Delay - 5000 ms
4,968 ms
5,032 ms
P / F
7
VTX - Live V Dropout Delay - 5000 ms
4,968 ms
5,032 ms
P / F
Sync-Check Verification (25)
Voltage Difference Accuracy = ±2% or ±1 V, whichever is greater
Step Voltage Difference Setting Low
Actual
Pickup
High
Actual
Dropout
Pass/Fail
5
VTX - Voltage Difference = 10%
107.8 V
112.2 V
P / F
6
VTP - Voltage Difference = 10%
107.8 V
112.2 V
P / F
Slip Angle Accuracy = ±
Step Slip Angle Setting Low
Actual
Pickup
High
Actual
Dropout
Pass/Fail
7
Slip Angle = +10°
11°
P / F
7
Slip Angle = 10°
–9°
11°
P / F
Slip Frequency Accuracy = ±0.01 Hz
Step Slip Frequency Setting Low
Actual
Pickup
High
Actual
Dropout
Pass/Fail
8
VTP - Slip Frequency =
59.70 Hz
58.50 Hz 60.89 Hz
P / F
8
VTP - Slip Frequency =
60.30 Hz
59.09 Hz 61.50 Hz
P / F
9
VTX - Slip Frequency =
59.70 Hz
58.50 Hz 60.89 Hz
P / F
9
VTX - Slip Frequency =
60.30 Hz
59.09 Hz 61.50 Hz
P / F
BE1-11g Sync-Check (25) Test