9289900992 Rev F BE1-851 Modbus™ Protocol 3-23
47525-26 Fault Clearing Time FP
Read only:
0 if Fault Clearing Time Status is not 0 (not valid).
Time (xxx.xxx) in seconds if Fault Clearing Time Status is 0 (valid).
47527 Fault Breaker Operate Time Status SI
Read only:
0 if Valid Fault Breaker Operate Time (Registers 47528-29) value
1 if Unknown
2 if N/A; Out of range
3 if No operation
47528-29 Fault Breaker Operate Time FP
Read only:
0 if Fault Breaker Operate Time Status is not 0 (not valid).
Time (xxx.xxx) in seconds if Fault Breaker Operate Time Status is 0 (valid).
47530-31 Fault Phase A Current Magnitude FP
47533-34 Fault Phase B Current Magnitude FP
47536-37 Fault Phase C Current Magnitude FP
47539-40 Fault Residual Current Magnitude FP
47542-43 Fault Neg-Seq. Current Magnitude FP
Read only:
Value in amps
Report Template (RPT)
47595-719 Report Text
Read only:
ASCII string (illegal message response generated for invalid Report Focus
value).
Metering Parameters
49720 Part Number INT
Read only:
0 to 999
49726-27 Phase A Current Magnitude FP
49729-30 Phase B Current Magnitude FP
49732-33 Phase C Current Magnitude FP
49735-36 Residual Current Magnitude FP
49738-39 Neg-Seq Current Magnitude FP
Read only:
Value in amps
49835-54 Error Details ASC(40)
Read only:
ASCII string
49875-999 Contiguous Poll Block Mixed
Read only:
Mixed values