9289900992 Rev F BE1-851 Modbus™ Protocol 2-13
Holding Read/Write Data
Register Parameter Supported Format Notes
Legacy: Product Information
The range 44011 - 45626 is the original (legacy) BE1-851 Modbus™ map.
44011-18 Application Software Version Number R - ASC(14) LEG
44021-27 Boot Software Version Number R - ASC(14) LEG
44031-37 Serial Number R - ASC(14) LEG
44046-56 Style Number R - ASC(22) LEG
44061 Part Number R - INT LEG
44081-85 Model Number R - ASC(10) LEG
44171-86 Customer Identification 1 (Relay ID) R - ASC(32) LEG
44187-202 Customer Identification 2 (Station ID) R - ASC(32) LEG
Legacy: Time and Date
44241 Date and Time - Day R W INT LEG
44242-43 Date and Time - Milliseconds R W DP LEG
Legacy: Breaker Duty
44251-52 Breaker Duty Phase A R W DP LEG
44253-54 Breaker Duty Phase B R W DP LEG
44255-56 Breaker Duty Phase C R W DP LEG
44261-62 Breaker Operations Counter R W DP LEG
Legacy: Select Before Operate (SBO) and Control Commands
44301 Control Select R W INT LEG
44303 Control Operate R W INT LEG
Legacy: Metering - Primary Parameters
44401-02 Phase A Current Magnitude R - DP LEG
44404-05 Phase B Current Magnitude R - DP LEG
44407-08 Phase C Current Magnitude R - DP LEG
44410-11 Neutral Current Magnitude R - DP LEG
44413-14 Negative Sequence Current Magnitude R - DP LEG
Legacy: Reporting
44601-02 Peak Demand Current - Phase A R W DP LEG
44603 Peak Demand Current - Day R - INT TS,LEG
44604-05 Peak Demand Current - Millisecond R - DP TS,LEG
44606-07 Peak Demand Current - Phase B R W DP LEG
44608 Peak Demand Current - Day R - INT TS,LEG
44609-10 Peak Demand Current - Millisecond R - DP TS,LEG
44611-12 Peak Demand Current - Phase C R W DP LEG
44613 Peak Demand Current - Day R - INT TS,LEG
44614-15 Peak Demand Current - Millisecond R - DP TS,LEG
44616-17 Peak Demand Current - Neutral R W DP LEG
44618 Peak Demand Current - Day R - INT TS,LEG
44619-20 Peak Demand Current - Millisecond R - DP TS,LEG
Komentarze do niniejszej Instrukcji