3-10 BE1-851 Modbus™ Protocol 9289900992 Rev F
40608-09 Programmable 51 Curve Constant A Delay FP
Read and Write:
0.0000 to 600.0000
40610-11 Programmable 51 Curve Constant B Delay FP
Read and Write:
0.0000 to 25.0000
40612-13 Programmable 51 Curve Constant C Delay FP
Read and Write:
0.0000 to 1.0000
40614-15 Programmable 51 Curve Constant N Delay FP
Read and Write:
0.5000 to 2.5000
40616-17 Programmable 51 Curve Constant R Delay FP
Read and Write:
0.0000 to 30.0000
40618 Input 1 Contact Recognition Time Delay SI
40619 Input 1 Contact Debounce Time Delay SI
40620 Input 2 Contact Recognition Time Delay SI
40621 Input 2 Contact Debounce Time Delay SI
40622 Input 3 Contact Recognition Time Delay SI
40623 Input 3 Contact Debounce Time Delay SI
40624 Input 4 Contact Recognition Time Delay SI
40625 Input 4 Contact Debounce Time Delay SI
Read and Write:
4 to 255 milliseconds
40746-870 Contiguous Poll Block Assignments INT
Read and Write:
0 if unassigned
1 to 9874: Holding Register 40001 to 49874
Note: To read the data from the registers programmed in this block, Contiguous Poll
Block registers 49875 to 49999 must be read.
40871 Setting Group Control On Time INT
Read and Write:
0 to 10 seconds
40872 Setting Group 1 Automatic Control Switch Time SI
40874 Setting Group 1 Automatic Control Return Time SI
40877 Setting Group 2 Automatic Control Switch Time SI
40879 Setting Group 2 Automatic Control Return Time SI
40882 Setting Group 3 Automatic Control Switch Time SI
40884 Setting Group 3 Automatic Control Return Time SI
Read and Write:
0 to 60 minutes
40873 Setting Group 1 Automatic Control Switch Level SI
40875 Setting Group 1 Automatic Control Return Level SI
40878 Setting Group 2 Automatic Control Switch Level SI
40880 Setting Group 2 Automatic Control Return Level SI
40883 Setting Group 3 Automatic Control Switch Level SI
40885 Setting Group 3 Automatic Control Return Level SI
Read and Write:
0 to 150%
Serial Port Setting Parameters
40962 Serial Port 0 Baud Rate INT
40971 Serial Port 1 Baud Rate INT
40980 Serial Port 2 Baud Rate INT