14 9424200774 Rev B
Register Table BE1-11
SBO Select
Name
Description
Register
Type
Bytes
Writable
Range
43-1
Select
600
Uint32
4
R W
Set=1
Reset=2
Pulse=3
43-2
Select
602
Uint32
4
R W
Set=1
Reset=2
Pulse=3
43-3
Select
604
Uint32
4
R W
Set=1
Reset=2
Pulse=3
43-4
Select
606
Uint32
4
R W
Set=1
Reset=2
Pulse=3
43-5
Select
608
Uint32
4
R W
Set=1
Reset=2
Pulse=3
101
Select
610
Uint32
4
R W
Trip=1
Close=2
Local Contacts
Contact Output 1 Override State Select
612
Uint8
1
R W
Off=0
On=1
Local Contacts
Contact Output 2 Override State Select
613
Uint8
1
R W
Off=0
On=1
Local Contacts
Contact Output 3 Override State Select
614
Uint8
1
R W
Off=0
On=1
Local Contacts
Contact Output 4 Override State Select
615
Uint8
1
R W
Off=0
On=1
Local Contacts
Contact Output 5 Override State Select
616
Uint8
1
R W
Off=0
On=1
Local Contacts
Contact Output A Override State Select
617
Uint8
1
R W
Off=0
On=1
Settings Group
Select
618
Int32
4
R W
Settings Group 0=0
Settings Group 1=1
Settings Group 2=2
Settings Group 3=3
Settings Group
Direct Operate
620
Int32
4
R W
Settings Group 0=0
Settings Group 1=1
Settings Group 2=2
Settings Group 3=3
Local Contacts
Contact Output 6 Override State Select
622
Uint8
1
R W
Off=0
On=1
Local Contacts
Contact Output 7 Override State Select
623
Uint8
1
R W
Off=0
On=1
Local Contacts
Contact Output 8 Override State Select
624
Uint8
1
R W
Off=0
On=1
SBO Operate
Name
Description
Register
Type
Bytes
Writable
Range
43-1
Operate
700
Uint32
4
R W
Set=1
Reset=2
Pulse=3
43-2
Operate
702
Uint32
4
R W
Set=1
Reset=2
Pulse=3
43-3
Operate
704
Uint32
4
R W
Set=1
Reset=2
Pulse=3
43-4
Operate
706
Uint32
4
R W
Set=1
Reset=2
Pulse=3
43-5
Operate
708
Uint32
4
R W
Set=1
Reset=2
Pulse=3
101
Operate
710
Uint32
4
R W
Trip=1
Close=2
Local Contacts
Contact Output 1 Override State Operate
712
Uint8
1
R W
Off=0
On=1
Local Contacts
Contact Output 2 Override State Operate
713
Uint8
1
R W
Off=0 On=1
Local Contacts
Contact Output 3 Override State Operate
714
Uint8
1
R W
Off=0
On=1
Local Contacts
Contact Output 4 Override State Operate
715
Uint8
1
R W
Off=0
On=1
Local Contacts
Contact Output 5 Override State Operate
716
Uint8
1
R W
Off=0
On=1
Local Contacts
Contact Output A Override State Operate
717
Uint8
1
R W
Off=0
On=1