9424200774 Rev B 123
BE1-11 Register Table
Name
Description
Group
Register
Type
Bytes
Writable
Unit
Range
Style
Analog Input Protection 7
Mode
SG2
23858
Uint32
4
R W
n/a
Disabled=0
Over=1
Under=2
FGIMT
Analog Input Protection 7
Source
SG2
23860
Uint32
4
R W
n/a
Module 1 Input 1=0
Module 1 Input 2=1
Module 1 Input 3=2
Module 1 Input 4=3
Module 2 Input 1=4
Module 2 Input 2=5
Module 2 Input 3=6
Module 2 Input 4=7
FGIMT
Analog Input Protection 7
Pickup
SG2
23862
Float
4
R W
n/a
-999999.9 - 999999.9
FGIMT
Analog Input Protection 7
Time Delay
SG2
23864
Float
4
R W
Millisecond
0 - 60000
FGIMT
Analog Input Protection 7
Inhibit Level
SG2
23866
Float
4
R W
n/a
-99999.9 - 99999.9
FGIMT
Analog Input Protection 7
Mode
SG3
23868
Uint32
4
R W
n/a
Disabled=0
Over=1
Under=2
FGIMT
Analog Input Protection 7
Source
SG3
23870
Uint32
4
R W
n/a
Module 1 Input 1=0
Module 1 Input 2=1
Module 1 Input 3=2
Module 1 Input 4=3
Module 2 Input 1=4
Module 2 Input 2=5
Module 2 Input 3=6
Module 2 Input 4=7
FGIMT
Analog Input Protection 7
Pickup
SG3
23872
Float
4
R W
n/a
-999999.9 - 999999.9
FGIMT
Analog Input Protection 7
Time Delay
SG3
23874
Float
4
R W
Millisecond
0 - 60000
FGIMT
Analog Input Protection 7
Inhibit Level
SG3
23876
Float
4
R W
n/a
-99999.9 - 99999.9
FGIMT
Analog Input Protection 8
Mode
SG0
23878
Uint32
4
R W
n/a
Disabled=0
Over=1
Under=2
FGIMT
Analog Input Protection 8
Source
SG0
23880
Uint32
4
R W
n/a
Module 1 Input 1=0
Module 1 Input 2=1
Module 1 Input 3=2
Module 1 Input 4=3
Module 2 Input 1=4
Module 2 Input 2=5
Module 2 Input 3=6
Module 2 Input 4=7
FGIMT
Analog Input Protection 8
Pickup
SG0
23882
Float
4
R W
n/a
-999999.9 - 999999.9
FGIMT
Analog Input Protection 8
Time Delay
SG0
23884
Float
4
R W
Millisecond
0 - 60000
FGIMT
Analog Input Protection 8
Inhibit Level
SG0
23886
Float
4
R W
n/a
-99999.9 - 99999.9
FGIMT
Analog Input Protection 8
Mode
SG1
23888
Uint32
4
R W
n/a
Disabled=0
Over=1
Under=2
FGIMT
Analog Input Protection 8
Source
SG1
23890
Uint32
4
R W
n/a
Module 1 Input 1=0
Module 1 Input 2=1
Module 1 Input 3=2
Module 1 Input 4=3
Module 2 Input 1=4
Module 2 Input 2=5
Module 2 Input 3=6
Module 2 Input 4=7
FGIMT
Analog Input Protection 8
Pickup
SG1
23892
Float
4
R W
n/a
-999999.9 - 999999.9
FGIMT
Analog Input Protection 8
Time Delay
SG1
23894
Float
4
R W
Millisecond
0 - 60000
FGIMT
Analog Input Protection 8
Inhibit Level
SG1
23896
Float
4
R W
n/a
-99999.9 - 99999.9
FGIMT
Analog Input Protection 8
Mode
SG2
23898
Uint32
4
R W
n/a
Disabled=0
Over=1
Under=2
FGIMT
Analog Input Protection 8
Source
SG2
23900
Uint32
4
R W
n/a
Module 1 Input 1=0
Module 1 Input 2=1
Module 1 Input 3=2
Module 1 Input 4=3
Module 2 Input 1=4
Module 2 Input 2=5
Module 2 Input 3=6
Module 2 Input 4=7
FGIMT
Analog Input Protection 8
Pickup
SG2
23902
Float
4
R W
n/a
-999999.9 - 999999.9
FGIMT
Analog Input Protection 8
Time Delay
SG2
23904
Float
4
R W
Millisecond
0 - 60000
FGIMT
Analog Input Protection 8
Inhibit Level
SG2
23906
Float
4
R W
n/a
-99999.9 - 99999.9
FGIMT
Analog Input Protection 8
Mode
SG3
23908
Uint32
4
R W
n/a
Disabled=0
Over=1
Under=2
FGIMT
Analog Input Protection 8
Source
SG3
23910
Uint32
4
R W
n/a
Module 1 Input 1=0
Module 1 Input 2=1
Module 1 Input 3=2
Module 1 Input 4=3
Module 2 Input 1=4
Module 2 Input 2=5
Module 2 Input 3=6
Module 2 Input 4=7
FGIMT